Refrigerant leak check
The law sets the interval by charge size and gives you a longer one for fitting detection. That is the conversion on offer: fit the detector, halve the visits, keep the log.
- Condition that replaces the interval
- Partly. Fixed leak detection in the plant room and an automatic charge monitor on the system detect a leak continuously; the periodic leak check is set by F-gas or refrigerant law by charge size and cannot be dropped, though fixed detection doubles the permitted interval.
- Reading that proves it
- Refrigerant charge (kg) against nameplate, fixed detector reading (ppm), superheat and subcooling
- Why the interval stays
- Leak check intervals are set by the EU F-gas Regulation and UK equivalent by charge in CO2 equivalent (every 12, 6 or 3 months, halved again without fixed detection), and by EPA Section 608 in the US.
- Evidence an auditor accepts
- Leak check record per system in the F-gas log with the charge, method, result and the technician's certification
- First move
- Record the charge in CO2 equivalent on every system so the correct statutory interval is visible on the register.
What it is evidence for
Clause references from a human-verified corpus licensed to Maintenance Log Converter. A clause marked reference is named, not reproduced.
Statutory intervals that must stay on the calendar ISO 45001:2018 9.1.2 · ISO 45001:2018 6.1.2.1 · ISO 45001:2018 8.1.2 · ISO 45001:2018 8.1.4.2 · ISO 55001:2014 4.2 · ISO 55001:2014 8.1
ISO 45001:2018 9.1.2 Evaluation of complianceThe organization establishes, implements and maintains processes for evaluating compliance with legal and other requirements, determining the frequency and methods for evaluation, evaluating compliance and taking action if needed, maintaining knowledge and understanding of its compliance status, and retaining documente...
ISO 45001:2018 6.1.2.1 Hazard identificationEstablish, implement and maintain a process for hazard identification that is ongoing and proactive. The process shall take into account work organization and social factors, routine and non routine activities, past incidents, emergency situations, people including workers, contractors, visitors and others, design of w...
ISO 45001:2018 8.1.2 Eliminating hazards and reducing OH&S risksThe organization establishes, implements and maintains processes for the elimination of hazards and reduction of OH&S risks using the hierarchy of controls: eliminate the hazard; substitute with less hazardous processes, operations, materials or equipment; use engineering controls and reorganization of work; use admini...
ISO 45001:2018 8.1.4.2 ContractorsThe organization coordinates its procurement processes with its contractors to identify hazards and to assess and control the OH&S risks arising from the contractors' activities and operations that impact the organization, from the organization's activities and operations that impact the contractors' workers, and from ...
ISO 55001:2014 4.2 Understanding the needs and expectations of stakeholdersThe organization determines the stakeholders relevant to the asset management system, their requirements and expectations with respect to asset management, the criteria for asset management decision-making, and the stakeholder requirements for recording financial and non-financial information and for reporting it inter...
ISO 55001:2014 8.1 Operational planning and controlThe organization plans, implements and controls the processes needed to meet requirements and to implement the actions determined in planning, including the actions to address risks and opportunities and the asset management plans. It establishes criteria for the processes, implements control in accordance with the cri...
Do this for your whole schedule