Cooling tower water treatment and legionella sampling
Chemistry converts; microbiology does not. Let the controller run the chemistry and log it, and keep the sampling calendar because the lab certificate is the compliance record.
What does cooling tower water treatment and legionella sampling involve?
Cooling tower water treatment and legionella sampling checks: conductivity, pH, oxidising biocide residual, dip slide or TVC result, legionella sample result. Observed by online water treatment controller for chemistry; laboratory analysis for microbiology. Cooling tower registration and periodic legionella sampling are required under state public health regulations in Australia and under HSG274 (COSHH) in the UK; monthly sampling is the usual minimum.
- Condition that replaces the interval
- Partly. Conductivity, pH, biocide residual and blowdown can be controlled and logged continuously; microbiological sampling stays on its interval because a lab result is the evidence the regulator wants.
- Reading that proves it
- Conductivity, pH, oxidising biocide residual, dip slide or TVC result, legionella sample result
- Why the interval stays
- Cooling tower registration and periodic legionella sampling are required under state public health regulations in Australia and under HSG274 (COSHH) in the UK; monthly sampling is the usual minimum.
- Evidence an auditor accepts
- Water treatment log with the daily chemistry and the monthly laboratory results per tower
- First move
- Log the controller readings into the same register as the lab results so an inspector sees the chemistry that preceded each sample.
What it is evidence for
Clause references from the published standards text. A clause marked reference is named, not reproduced.
Statutory intervals that must stay on the calendar ISO 45001:2018 9.1.2 · ISO 45001:2018 6.1.2.1 · ISO 45001:2018 8.1.2 · ISO 45001:2018 8.1.4.2 · ISO 55001:2014 4.2 · ISO 55001:2014 8.1
ISO 45001:2018 9.1.2 Evaluation of complianceThe organization sets up, runs and keeps processes for evaluating whether it complies with legal and other requirements. It decides how often and by what methods compliance is evaluated, carries out the evaluation and acts where needed, keeps up its knowledge and understanding of where it stands on compliance, and reta...
ISO 45001:2018 6.1.2.1 Hazard identificationSet up, run and keep a hazard identification process that is continuous and looks ahead. The process shall take into account: social factors and the way work is organized; activities that are routine and those that are not; incidents that have happened before; possible emergencies; people, including workers, contractor...
ISO 45001:2018 8.1.2 Eliminating hazards and reducing OH&S risksThe organization sets up, runs and keeps processes for removing hazards and lowering OH&S risks by working down the hierarchy of controls: first remove the hazard; next replace it with processes, operations, materials or equipment that are less hazardous; then apply engineering controls and reorganize the work; then ap...
ISO 45001:2018 8.1.4.2 ContractorsThe organization aligns its procurement processes with its contractors so that hazards are identified and the OH&S risks are assessed and controlled where they come from three sources: contractor activities and operations that affect the organization; the organization's own activities and operations that affect contrac...
ISO 55001:2014 4.2 Understanding the needs and expectations of stakeholdersThe organization identifies which stakeholders are relevant to its system for managing assets, and what they require and expect from asset management; it sets the criteria it will use to make asset management decisions; and it identifies what stakeholders require in the way of recorded financial and non-financial infor...
ISO 55001:2014 8.1 Operational planning and controlThe organization plans, carries out and controls the processes needed to satisfy requirements and to deliver three things: the asset management plans set out under 6.2, the actions on risks and opportunities decided under 6.1, and the preventive and corrective actions decided under clauses 10.1 and 10.2. It does so by ...